Figure 4: Power Distribution From Three-Phase Feed Wye Pdm To The Ac; Psms; Table 4: Ac Pdm Delta And Wye Current Requirements - Juniper MX2020 Hardware Manual

3d universal edge router
Hide thumbs Also See for MX2020:
Table of Contents

Advertisement

MX2020 3D Universal Edge Router Hardware Guide
8

Figure 4: Power Distribution from Three-Phase Feed Wye PDM to the AC

PSMs

AC PS_0
2800W
input
NE1
A1
B1
C1
The AC power subsystem is feed redundant, each PSM takes in two AC feeds and uses
one of the two. One AC feed is active at a time. If one feed fails, the PSM automatically
switches over to the other feed without disrupting system function, (see
Three-Phase Delta AC Power Distribution Module Description" on page
Three-Phase Wye AC Power Distribution Module Description" on page
AC Power Supply Module Description" on page
AC power
requirements—Table 4 on page 8
for the three–phase delta and wye power feeds.

Table 4: AC PDM Delta and Wye Current Requirements

Three–Phase
Voltage
Input Feed
200V
1
(minimum–nominal)
(line-to-line) for delta
2
(per phase)
200V
1
(minimum–nominal)
(line-to-neutral) for
2
wye (per phase)
NOTE:
This is the minimum required to provide 2.5KW per PSM. Based on
facilities guidelines, you should over-provision the MX2020 router. The two
numbers listed in the current columns reflect the distribution of phases
from the feed to PSM. For example, from one feed each phase goes to two
PSMs and from other feed each phase goes to only one PSM.
AC PS_1
AC PS_4
2800W
2800W
input
input
AC PS_3
AC PS_2
AC PS_5
AC PS_6
2800W
2800W
2800W
2800W
input
input
input
46).
shows the MX2020 current requirements
Current Delta per
Three-Phase PDM
50A
25A
AC PS_7
2800W
input
AC PS_8
2800W
input
input
NE2
A2
B2
C2
"MX2020
42,
"MX2020
44, and
"MX2020
Current Wye per
Three-Phase PDM
30A
15A
Copyright © 2013, Juniper Networks, Inc.

Advertisement

Table of Contents
loading