Figure 40: Airflow Through Chassis - Juniper MX2020 Hardware Manual

3d universal edge router
Hide thumbs Also See for MX2020:
Table of Contents

Advertisement

Related
Documentation
Copyright © 2013, Juniper Networks, Inc.
chassis. If the cabinet contains a top or doors, perforations in these elements assist
with removing the hot air exhaust. For an illustration of chassis airflow, see
on page
73.
Install the router as close as possible to the front of the cabinet so that the cable
manager just clears the inside of the front door. This maximizes the clearance in the
rear of the cabinet for critical airflow.
Route and dress all cables to minimize the blockage of airflow to and from the chassis.

Figure 40: Airflow Through Chassis

Upper Fan trays
Card cage
Card cage
Airflow divider
Card cage
Lower fan trays
Clearance Requirements for Airflow and Hardware Maintenance for the MX2020 Router
on page 71
MX2020 Cabinet Size and Clearance Requirements on page 72
MX2020 Rack Requirements on page 69
MX2020 Rack-Mounting Hardware on page 19
Chapter 4: Preparing the Site for MX2020 Router Installation
Power
supply
cooling
Figure 40
73