CHAPTER 6
Installing the MX2020 Router Mounting
Hardware
Installing the MX2020 Mounting Hardware for a Four-Post Rack or Cabinet
Installing Cage Nuts, If Needed
Copyright © 2013, Juniper Networks, Inc.
Installing the MX2020 Mounting Hardware for a Four-Post Rack or Cabinet on page 81
Installing Cage Nuts, If Needed on page 81
1.
Installing the Four-Post Mounting Shelf on page 83
2.
Insert cage nuts, if needed, into the holes listed in
page
82. The hole distances are relative to the standard U division on the rack that is
aligned with the bottom of the mounting shelf.
To install cage nuts in a four-post rack:
On the rear side of both rack rails, insert cage nuts in the holes specified for the
1.
four-post mounting shelf. Install the cage nuts in the front of the front rail (see
29 on page
81).
On the front side of both rack rails, insert cage nuts in the holes specified for mounting
2.
the chassis. Install the cage nuts in the front of the front rail (see
Table 29: Mounting Hole Locations for Installing the Four-Post Mounting
Shelf
Hole
Distance Above U Division
6
3.25 in. (8.3 cm)
5
2.63 in. (6.7 cm)
4
2.00 in. (5.1 cm)
3
1.50 in. (3.8 cm)
2
0.88 in. (2.2 cm)
Table 29 on page 81
and
Table 30 on
Table 30 on page
Four-Post Rack
Mounting Shelf
1.86 U
X
1.5 U
X
1.14 U
X
0.86 U
X
0.50 U
X
Table
82).
81