Copyright © 2013, Juniper Networks, Inc.
NOTE:
Removing the cables from the DC cable manager is not necessary
to access the air filter.
CAUTION:
Do not run the router for more than 2 minutes without the air
filter in place.
Grasp the handle on the air filter, and pull the air filter straight out from the chassis.
3.
NOTE:
The air filter has a built-in handle.
Slide the air filter out of the chassis as shown in
4.
Figure 96: Removing the Lower Air Filter from the Chassis
To remove the middle card cage cable manager air filter—MX2000-CBL-MID-S:
Attach an electrostatic discharge (ESD) grounding strap to your bare wrist, and connect
1.
the strap to one of the ESD points on the chassis.
Move the cables from the middle card cage cable manager, if necessary.
2.
Loosen the two captive screws located on the front of the middle card cage cable
3.
manager door.
CAUTION:
Do not run the router for more than 2 minutes without the air
filter in place.
Chapter 13: Replacing MX2020 Router Hardware Components
Figure 96 on page
D
223.
223