Figure 72: Connecting Power To A Three-Phase Delta Ac Power Distribution; Module - Juniper MX2020 Hardware Manual

3d universal edge router
Hide thumbs Also See for MX2020:
Table of Contents

Advertisement

Copyright © 2013, Juniper Networks, Inc.

Figure 72: Connecting Power to a Three-Phase Delta AC Power Distribution

Module

NOTE:
The three-phase delta AC PDM terminal blocks will be flipped
depending on which slot the PDM gets plugged into.
NOTE:
The color of each AC power wire might vary. The MX2020 chassis
is not sensitive to phase rotation sequence—either CW or CCW will operate
correctly.
To connect wires to the terminal block that serves three PSMs:
a. Insert the grounding wire into the grounding point labeled
b. Insert the wire into the input terminal labeled
c. Insert the wire into the input terminal labeled
d. Insert the wire into the input terminal labeled
Verify that the power cable connections are correct.
13.
Reinstall the metal PDM wiring cover, and using a number 2 Phillips (+) screwdriver,
14.
tighten the four captive screws on the metal AC wiring compartment.
Use the provided plastic cable tie to fasten the AC power cord to the PDM.
15.
Chapter 9: Grounding and Providing Power to the MX2020 Router
.
A2
B2
.
.
C2
GND
.
119