E5GN


SPECIFICATION SETTING

(AFTER TURNING ON POWER)

Initial Setting Level

This level is used for setting basic specifications of the
Temperature Controller. Using this level, set the input type for
selecting the input to be connected such as the thermocouple or
platinum resistance thermometer and set the range of set point
and the alarm mode.
Power ON
Adjustment level
Operation level
key
Less than 1 second
key
key
1 second min.
3 second min.
Initial setting
Communications
level
setting level
key
Less than 1 second
key
Password input
1 second min.
set value "-169"
*3
Advanced function
setting level
Password input
set value "1201"
Calibration level
The move from the operation level to the initial setting level,
press
key for three seconds or more.
The initial setting level is not displayed when
"initial/communications protection" is set to "2." This initial setting
level can be used when "initial setting/communications
protection" is set to "0" or "1."
The "scaling upper limit," "scaling lower limit," and "decimal point"
parameters are displayed when an analog voltage input is
selected as the input type.
+
key
1 second min.
Control stops.
Protect level
Initial setting level
Input type
Scaling upper limit
Scaling lower limit
Decimal point
Temperature unit
Set point upper limit
Set point lower limit
PID / ON/OFF
Standard/heating and
cooling
ST
Control period (heat)
Control period (cool)
Direct/reverse operation
Alarm 1 type
Alarm 2 type
Move to advanced
function setting level
To return to the operation level, press the
one second
*
Not displayed as default setting.
Note: 1. Displayed only with models provided with an alarm
function.
2. Displayed only with the E5CN provided with a two-
point alarm function.
3. Advanced function setting level is for E5CN models
only.
E5GN
 : ON/OFF control
 : PID control
 : Standard
 : Heating/cooling
 : Enabled
 : Disabled
 : Reverse
operation
 : Direct
operation
key for longer than

Advertisement

Table of Contents
loading