Operation; Setting Levels Diagram - Omron E5CD-B-800 Series Instruction Manual

Digital temperature controller (simple type)
Table of Contents

Advertisement

Operation

Setting Levels Diagram

This diagram shows all of the setting levels. To move to the advanced function setting level and calibration level, you must enter passwords. Some
parameters are not displayed depending on the protect level setting and the conditions of use.
Control stops when you move from the operation level to the initial setting level.
Manual Control
Level
Used to set the MV
manually.
*1. Set the PF Setting parameter to a-m (Auto/Manual).
*2. The No. 1 display will flash when the keys are pressed for 1 s or longer.
*3. Set the PF Setting parameter to pfdp (monitor/setting items).
Only when Manual Mode was used
just before power OFF
Power ON
Press the O Key
for at least 1 s or
Level changes
the S Key for at
*1
least 1 s
automatically.
Operation Level
Used for SP, alarm
O Key for at
values, and other basic
least 3 s while
settings and monitoring.
a-m is
*2
displayed.
*1
S Key for at least 1 s
Press the O Key
for at least 1 s.
Initial Setting Level
Used to set the input type
and other basic settings.
Release protection and
then enter the password
(−169) for the amoV
(Move to Advanced
Advanced Function
Setting Level)
parameter.
Setting Level
Used to set application functions.
Enter the password (1201)
while cmov (Move to
Calibration Level
parameter) is displayed.
Calibration Level
Press the O + M Keys for
at least 1 s
Used to set protection
for operations.
Adjustment Level
Press the O Key once.
Used to change adjustment
parameters (PID constants,
adjustment sensitivity, etc.).
*3
Press the S Key.
Press the S Key.
Monitor/Setting
Item Level
Press the O Key for
Used to display
*2
at least 3 s
specified monitor
and setting items.
Control and auxiliary outputs stop.
Press the O Key for less than 1 s.
(models with communications only).
Press the O Key for at least 1 s.
E5@D-800
Protect Level
Press the O + M
*2
Keys for at least 3 s.
*3
Communications
Setting Level
Used to set up
communications.
39