Commissioning
4.4 Establishing an online connection to the drive
Selecting the preferred PG/PC interface
If you prefer to use a specific network interface of your PG/PC to establish an online
connection, you can preset this interface.
1. Select the "Options > Settings" menu.
The settings of the TIA Portal are displayed.
2. Select the "Online and diagnostics" entry in the area navigation.
3. In the "Preset connection path for online access" area, specify the type of the PG/PC
interface as well as the interface itself.
4. Enable the option "Display dialog for setting the default connection path for the online
access".
4.4.2

Connection via standard Ethernet interface

Requirement
You have created a project in the TIA Portal and inserted a CU320-2 PN. The devices are
cabled via the Ethernet commissioning interface X127 - therefore facilitating an online
connection.
As the Ethernet commissioning interface has already been assigned an IP address, you can
go online directly.
If you are not using a new project, and devices have already been created, in the project,
check the IP address of the interface in the inspector window at "Properties > General >
Ethernet addresses" and the IP address assigned to the device. The addresses and subnet
masks must be identical.
Quick search via "Online access"
In order to obtain a fast overview, you can start a search in "Online access" under the
required interface. If the wiring to your drive is error-free and you have wired the correct drive
(LED flashing for checking), the drive is displayed with the appropriate IP address.
Figure 4-31
92
Online access
Commissioning Manual, (IH3), 07/2016, 6SL3097-4AA10-0BP0
Commissioning with Startdrive