Application planning
4.12 Star connection of the motor or 87 Hz delta connection
4.12
Star connection of the motor or 87 Hz delta connection
Overview
In the case of a 400‑V power supply, the motor can be operated on the converter in either a star
or a delta connection.
In a star connection, the motor is operated with its rated values.
In a delta connection, the motor is operated with a voltage and frequency above its rated
values.
Description of function
Star connection
Figure 4-4
In a star connection, the motor can be loaded with its rated torque M
frequency f
The rated voltage U
The motor goes into field weakening above the rated frequency. In field weakening, the
available motor torque decreases proportionally with 1/f. In field weakening, the available
power remains constant.
Delta connection
Figure 4-5
76
Motor in star connection
.
N
= 400 V is available at the rated frequency f
N
Motor in delta connection with 87 Hz characteristic
 = 50 Hz.
N
Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB
in the range 0 ... rated
N
SINAMICS G220 converter