Main Menu - Application Functions - TR200 - Group 22

This group contains parameters used for monitoring TR200 applications.
22-00 External Interlock Delay
Range:
0 s*
[0 - 600 s]
22-2* No-Flow Detection
The frequency converter includes functions for detecting if the load conditions in the system allow the motor to
be stopped:
*Low Power Detection
*Low Speed Detection
One of these two signals must be active for a set time (par.22-24
place. Possible actions to select (par.22-23
No Flow Detection:
This function is used for detecting a no flow situation in pump systems where all valves can be closed. Can be
used both when controlled by the integrated PI controller in the frequency converter or an external PI controller.
Actual configuration must be programmed in par.1-00
Configuration mode for
-
Integrated PI Controller: Closed Loop
-
External PI Controller: Open Loop
NOTICE
Carry out No Flow tuning before setting the PI controller parameters!
TR200 Programming Guide
Function:
Only relevant if one of the digital inputs in parameter group 5-1* has
External Interlock
been programmed for
will introduce a delay after the signal has been removed from the digital
input programmed for External Interlock, before reaction takes place.
No-Flow
Function): No action, Warning, Alarm, Sleep Mode.
Configuration
Parameter Description
[7]. The External Interlock Timer
No-Flow
Delay) before selected action takes
Mode.
213