6-16 Terminal 53 Filter Time Constant
Range:
0.001 s* [0.001 - 10.000 s]
6-17 Terminal 53 Live Zero
Option:
[0]
Disabled
[1] *
Enabled
6-2* Analog Input 2
Parameters for configuring the scaling and limits for analog input 2 (terminal 54).
6-20 Terminal 54 Low Voltage
Range:
0.07 V* [0.00 - par. 6-21 V]
6-21 Terminal 54 High Voltage
Range:
10.00 V* [par. 6-20 - 10.00 V]
6-22 Terminal 54 Low Current
Range:
4.00
[0.00 - par. 6-23 mA]
mA*
6-23 Terminal 54 High Current
Range:
20.00
[par. 6-22 - 20.00 mA]
mA*
6-24 Terminal 54 Low Ref./Feedb. Value
Range:
0.000 N/
[-999999.999 - 999999.999
A*
N/A]
TR200 Programming Guide
Function:
Enter the time constant. This is a first-order digital low pass filter time
constant for suppressing electrical noise in terminal 53. A high time con-
stant value improves dampening but also increases the time delay
through the filter.
This parameter cannot be adjusted while the motor is running.
Function:
This parameter makes it possible to disable the Live Zero monitoring.
E.g. to be used if the analog outputs are used as part of a de-central I/O
system (e.g. when not as part of any frequency converter related control
functions, but feeding a Building Management system with data).
Function:
Enter the low voltage value. This analog input scaling value should cor-
respond to the low reference/feedback value, set in par.6-24
Low Ref./Feedb.
Value.
Function:
Enter the high voltage value. This analog input scaling value should cor-
respond to the high reference/feedback value set in par.6-25
High Ref./Feedb.
Value.
Function:
Enter the low current value. This reference signal should correspond to
the low reference/feedback value, set in par.6-24
Feedb.
Value. The value must be set at >2 mA in order to activate the Live
Zero Time-out Function in par.6-01
Function:
Enter the high current value corresponding to the high reference/feed-
back value set in par.6-25
Terminal 54 High Ref./Feedb.
Function:
Enter the analog input scaling value that corresponds to the low voltage/
low current value set in par.6-20
6-22
Terminal 54 Low
Current.
Parameter Description
Terminal 54 Low Ref./
Live Zero Timeout
Function.
Value.
Terminal 54 Low Voltage
and par.
Terminal 54
Terminal 54