Trane TR200 Series Programming Manual page 182

Hide thumbs Also See for TR200 Series:
Table of Contents

Advertisement

Note
When mounting an Analog I/O MCB 115 option card, a battery back-up of date and time is included.
18-1* Fire Mode Log
The log covers the latest 10 faults which have been suppressed by the Fire Mode function. See
Mode
. The log can be viewed either via the below parameters or by pressing the Alarm Log button on the
keypad and select Fire Mode Log. It is not possible to reset the Fire Mode Log.
18-10 Fire Mode Log: Event
Range:
0 N/A*
[0 - 255 N/A]
18-11 Fire Mode Log: Time
Range:
0 s*
[0 - 2147483647 s]
18-12 Fire Mode Log: Date and Time
Range:
0 N/A*
[0 - 0 N/A]
TR200 Programming Guide
Function:
This parameter contains an array with 10 elements. The number read
represent an error code, which corresponds to a specific alarm. This can
be found in the Troubleshooting section in the Design Guide.
Function:
This parameter contains an array with 10 elements. The parameter
shows at which time the logged event occurred. Time is measured in
seconds since the first start of the motor.
Function:
This parameter contains an array with 10 elements. The parameter
shows at which date and time the logged event occurred. The function
relies on that the actual date and time has been set in par.0-70
Time. Note: There is no build in battery back up of the clock. An external
back up must be used, eg the one in the MCB 115 Analog I/O option card.
See Clock Settings, 0-7*.
Parameter Description
par. 24-0*, Fire
Date and
181

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents