6-01 Live Zero Timeout Function
Option:
[0] *
Off
[1]
Freeze output
[2]
Stop
[3]
Jogging
[4]
Max. speed
[5]
Stop and trip
TR200 Programming Guide
Function:
Select the time-out function. The function set in par.6-01
out Function
will be activated if the input signal on terminal 53 or 54 is
below 50% of the value in par.6-10
6-12
Terminal 53 Low
Current, par.6-20
6-22
Terminal 54 Low Current
Zero Timeout
Time. If several time-outs occur simultaneously, the fre-
quency converter prioritises the time-out functions as follows:
1.
par.6-01
Live Zero Timeout Function
2.
par.8-04
Control Timeout Function
The output frequency of the frequency converter can be:
[1] frozen at the present value
[2] overruled to stop
[3] overruled to jog speed
[4] overruled to max. speed
[5] overruled to stop with subsequent trip
Parameter Description
Live Zero Time-
Terminal 53 Low
Voltage, par.
Terminal 54 Low Voltage
for a time period defined in par.6-00
or par.
Live