Trane TR200 Series Programming Manual page 130

Hide thumbs Also See for TR200 Series:
Table of Contents

Advertisement

8-32 Baud Rate
Option:
[0]
2400 Baud
[1]
4800 Baud
[2] *
9600 Baud
[3]
19200 Baud
[4]
38400 Baud
[5]
57600 Baud
[6]
76800 Baud
[7]
115200 Baud
Default refers to the FC Protocol.
8-33 Parity / Stop Bits
Option:
[0] *
Even Parity, 1 Stop Bit
[1]
Odd Parity, 1 Stop Bit
[2]
No Parity, 1 Stop Bit
[3]
No Parity, 2 Stop Bits
8-35 Minimum Response Delay
Range:
10. ms* [5. - 10000. ms]
8-36 Maximum Response Delay
Range:
10001.
[11. - 10001. ms]
ms*
8-37 Maximum Inter-Char Delay
Range:
25.00
[0.00 - 35.00 ms]
ms*
TR200 Programming Guide
Function:
Baud rate selection depends on Protocol selection in par.8-30 Protocol.
Function:
Parity and Stop Bits for the protocol par.8-30
For some of the protocols, not all options will be visible. Default depends
on the protocol selected.
Function:
Specify the minimum delay time between receiving a request and trans-
mitting a response. This is used for overcoming modem turnaround
delays.
Function:
Specify the maximum permissible delay time between transmitting a re-
quest and receiving a response. Exceeding this delay time will cause
control word time-out.
Function:
Specify the maximum permissible time interval between receipt of two
bytes. This parameter activates time-out if transmission is interrupted.
Parameter Description
Protocol
using the FC Port.