20-00 Feedback 1 Source
Option:
[0]
No function
[1]
Analog input 53
[2] *
Analog input 54
[3]
Pulse input 29
[4]
Pulse input 33
[7]
Analog input X30/11
[8]
Analog input X30/12
[9]
Analog Input X42/1
[10]
Analog Input X42/3
[11]
Analog Input X42/5
[100]
Bus feedback 1
[101]
Bus feedback 2
[102]
Bus feedback 3
NOTE: If a feedback is not used, its source must be set to
how the three possible feedbacks will be used by the PID Controller.
20-01 Feedback 1 Conversion
Option:
[0] *
Linear
[1]
Square root
[2]
Pressure to temperature
20-02 Feedback 1 Source Unit
Option:
[0] *
[1]
%
[5]
PPM
TR200 Programming Guide
Function:
Up to three different feedback signals can be used to provide the feed-
back signal for the frequency converter's PID Controller.
This parameter defines which input will be used as the source of the first
feedback signal.
Analog input X30/11 and Analog input X30/12 refer to inputs on the op-
tional General Purpose I/O board.
No Function
Function:
This parameter allows a conversion function to be applied to Feedback
1.
Linear
[0] has no effect on the feedback.
Square root
[1] is commonly used when a pressure sensor is used to pro-
flow
vide flow feedback ( (
Pressure to temperature
[2] is used in compressor applications to provide
temperature feedback using a pressure sensor. The temperature of the
refrigerant is calculated using the following formula:
A
Temperature
=
(
ln
(
Pe
+ 1 ) −
frigerant-specific constants. The refrigerant must be selected in par.
20-30 Refrigerant. par.20-21
low the values of A1, A2 and A3 to be entered for a refrigerant that is not
listed in par.20-30 Refrigerant.
Function:
This parameter determines the unit that is used for this Feedback Source,
prior to applying the feedback conversion of par.20-01
version. This unit is not used by the PID Controller.
Parameter Description
[0]. par.20-20
Feedback Function
pressure
) ).
2
A
3 , where A1, A2 and A3 are re-
A
1 )
Setpoint 1
through par.20-23
determines
Setpoint 3
al-
Feedback 1 Con-
183

Hide quick links:

Advertisement

Table of Contents
loading