14-21 Automatic Restart Time
Range:
10 s*
[0 - 600 s]
14-22 Operation Mode
Option:
[0] *
Normal operation
[1]
Control card test
TR200 Programming Guide
Function:
Enter the time interval from trip to start of the automatic reset function.
This parameter is active when par.14-20
reset
[1] - [13].
Function:
Use this parameter to specify normal operation, to perform tests or to
initialize all parameters except par.15-03
Temp's
and par.15-05
Over
power is cycled (power off-power on) to the frequency converter.
Normal operation
Select
[0] for normal operation of the frequency con-
verter with the motor in the selected application.
Control card test
Select
[1] to test the analog and digital inputs and outputs
and the +10 V control voltage. The test requires a test connector with
internal connections.
Use the following procedure for the control card test:
Control card test
1.
Select
2.
Disconnect the mains supply and wait for the light in the display to
go out.
3.
Set switches S201 (A53) and S202 (A54) = 'ON' / I.
4.
Insert the test plug (see below).
5.
Connect to mains supply.
6.
Carry out various tests.
7.
The results are displayed on the keypad and the frequency converter
moves into an infinite loop.
8.
par.14-22
Operation Mode
Carry out a power cycle to start up in Normal operation after a con-
trol card test.
If the test is OK:
keypad read-out: Control Card OK.
Disconnect the mains supply and remove the test plug. The green LED
on the control card will light up.
If the test fails:
keypad read-out: Control Card I/O failure.
Replace the frequency converter or control card. The red LED on the
control card is turned on. To test the plugs, connect/group the following
terminals as shown below: (18 - 27 - 32), (19 - 29 - 33) and (42 - 53 - 54).
Parameter Description
Reset Mode
is set to
Power
Up's, par.15-04
Volt's. This function is active only when the
[1].
is automatically set to Normal operation.