14-3* Current Limit Control
The frequency converter features an integral Current Limit Controller which is activated when the motor current,
and thus the torque, is higher than the torque limits set in par.4-16
4-17
Torque Limit Generator
When the current limit is reached during motor operation or regenerative operation, the frequency converter
will try to reduce torque below the preset torque limits as quickly as possible without losing control of the motor.
While the current control is active, the frequency converter can only be stopped by setting a digital input to
Coast inverse
Coast and reset inv.
[2] or
converter is no longer near the current limit.
By using a digital input set to
time, since the frequency converter is coasted.
14-30 Current Lim Ctrl, Proportional Gain
Range:
100 %* [0 - 500 %]
14-31 Current Lim Ctrl, Integration Time
Range:
0.020 s* [0.002 - 2.000 s]
14-32 Current Lim Ctrl, Filter Time
Range:
26.0
[1.0 - 100.0 ms]
ms*
14-4*Energy Optimizing
Parameters for adjusting the energy optimization level in both Variable Torque (VT) and Automatic Energy Op-
timization (AEO) mode.
Automatic Energy Optimization is only active if par.1-03
Optim. Compressor
Auto Energy Optim. VT
[2] or
14-40 VT Level
Range:
66 %*
[40 - 90 %]
14-41 AEO Minimum Magnetisation
Range:
40. %*
[40 - 75 %]
14-42 Minimum AEO Frequency
Range:
10 Hz*
[5 - 40 Hz]
TR200 Programming Guide
Mode.
[3]. Any signal on terminals 18 to 33 will not be active until the frequency
Coast inverse
Coast and reset inv.
[2] or
Function:
Enter the proportional gain value for the current limit controller. Selec-
tion of a high value makes the controller react faster. Too high a setting
leads to controller instability.
Function:
Controls the current limit control integration time. Setting it to a lower
value makes it react faster. A setting too low leads to control instability.
Function:
[3].
Function:
Enter the level of motor magnetisation at low speed. Selection of a low
value reduces energy loss in the motor, but also reduces load capability.
This parameter cannot be adjusted while the motor is running.
Function:
Enter the minimum allowable magnetisation for AEO. Selection of a low
value reduces energy loss in the motor, but can also reduce resistance
to sudden load changes.
Function:
Enter the minimum frequency at which the Automatic Energy Optimiza-
tion (AEO) is to be active.