16-38 SL Controller State
Range:
0 N/A*
[0 - 100 N/A]
16-39 Control Card Temp.
Range:
0 C*
[0 - 100 C]
16-40 Logging Buffer Full
Option:
[0] *
No
[1]
Yes
16-49 Current Fault Source
Range:
0 N/A*
[0 - 8 N/A]
After a short circuit alarm (imax2) or over current alarm (imax1 or phase imbalance) this will contain the power
card number associated with the alarm. It only holds one number so it will indicate the highest priority power
card number (master first). The value will persist on power cycle but if a new alarm occurs it will be overwritten
with the new power card number (even if it a lower priority number). The value will only be cleared when the
alarm log is cleared (i.e. a 3-finger reset would reset the readout to 0).
16-5* Ref. & Feedb.
Parameters for reporting the reference and feedback input.
16-50 External Reference
Range:
0.0 N/A* [-200.0 - 200.0 N/A]
16-52 Feedback [Unit]
Range:
0.000
[-999999.999 - 999999.999
Proc-
ProcessCtrlUnit]
essCtrlU-
nit*
16-53 Digi Pot Reference
Range:
0.00 N/
[-200.00 - 200.00 N/A]
A*
TR200 Programming Guide
Function:
View the state of the event under execution by the SL controller.
Function:
View the temperature on the control card, stated in °C.
Function:
View whether the logging buffer is full (see parameter group 15-1*). The
logging buffer will never be full when par.15-13
Log always
[0].
Function:
Value indicates source of current fault, including: short circuit, over cur-
rent and phase imbalance (from left): [1-4] Inverter, [5-8] Rectifier, [0] No
fault recorded
Function:
View the total reference, the sum of digital, analog, preset, bus and freeze
references, plus catch-up and slow-down.
Function:
View value of resulting feedback value after processing of Feedback 1-3
(see par.16-54
Feedback 1
16-56) in the feedback manager.
Feedback
See par. 20-0*
.
The value is limited by settings in par. 20-13 and par. 20-14. Units as set
in par.20-12
Reference/Feedback
Function:
View the contribution of the Digital Potentiometer to the actual reference.
Parameter Description
Logging Mode
[Unit], par.16-55
Feedback 2 [Unit]
Unit.
is set to
and par.
173

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents