Trane TR200 Series Programming Manual page 119

Hide thumbs Also See for TR200 Series:
Table of Contents

Advertisement

Parameter Description
6-25 Terminal 54 High Ref./Feedb. Value
Range:
100.000
[-999999.999 - 999999.999
N/A*
N/A]
6-26 Terminal 54 Filter Time Constant
Range:
0.001 s* [0.001 - 10.000 s]
6-27 Terminal 54 Live Zero
Option:
[0]
Disabled
[1] *
Enabled
6-3* Analog Input 3 MCB 101
Parameter group for configuring the scale and limits for analog input 3 (X30/11) placed on option module MCB
101.
6-30 Terminal X30/11 Low Voltage
Range:
0.07 V* [0.00 - par. 6-31 V]
6-31 Terminal X30/11 High Voltage
Range:
10.00 V* [par. 6-30 - 10.00 V]
6-34 Term. X30/11 Low Ref./Feedb. Value
Range:
0.000 N/
[-999999.999 - 999999.999
A*
N/A]
6-35 Term. X30/11 High Ref./Feedb. Value
Range:
100.000
[-999999.999 - 999999.999
N/A*
N/A]
118
Function:
Enter the analog input scaling value that corresponds to the high voltage/
high current value set in par.6-21
6-23
Terminal 54 High
Current.
Function:
Enter the time constant. This is a first-order digital low pass filter time
constant for suppressing electrical noise in terminal 54. A high time con-
stant value improves dampening but also increases the time delay
through the filter.
This parameter cannot be adjusted while the motor is running.
Function:
This parameter makes it possible to disable the Live Zero monitoring.
E.g. to be used if the analog outputs are used as part of a de-central I/O
system (e.g. when not as part of any frequency converter related control
functions, but feeding a Building Management System with data).
Function:
Sets the analog input scaling value to correspond to the low reference/
feedback value (set in par.6-34
Function:
Sets the analog input scaling value to correspond to the high reference/
feedback value (set in par.6-35
Function:
Sets the analog input scaling value to correspond to the low voltage val-
ue (set in par.6-30
Terminal X30/11 Low
Function:
Sets the analog input scaling value to correspond to the high voltage
value (set in par.6-31
Terminal X30/11 High
Terminal 54 High Voltage
Term. X30/11 Low Ref./Feedb.
Term. X30/11 High Ref./Feedb.
Voltage).
Voltage).
TR200 Programming Guide
and par.
Value).
Value).

Hide quick links: