Parameter Description
16-18 Motor Thermal
Range:
0 %*
[0 - 100 %]
16-22 Torque [%]
Range:
0 %*
[-200 - 200 %]
16-3* Drive Status
Parameters for reporting the status of the frequency converter.
16-30 DC Link Voltage
Range:
0 V*
[0 - 10000 V]
16-32 Brake Energy /s
Range:
0.000
[0.000 - 10000.000 kW]
kW*
16-33 Brake Energy /2 min
Range:
0.000
[0.000 - 10000.000 kW]
kW*
16-34 Heatsink Temp.
Range:
0 C*
[0 - 255 C]
16-35 Inverter Thermal
Range:
0 %*
[0 - 100 %]
16-36 Inv. Nom. Current
Range:
10.00 A* [0.01 - 10000.00 A]
16-37 Inv. Max. Current
Range:
16.00 A* [0.01 - 10000.00 A]
172
Function:
View the calculated thermal load on the motor. The cut-out limit is 100%.
The basis for calculation is the ETR function selected in par.1-90
Thermal
Protection.
Function:
This is a read out parameter only.
Shows the actual torque yielded in percentage of the rated torque, based
on the setting of the motor size and rated speed in par.1-20
[kW]
or par.1-21
Motor Power [HP]
This is the value monitored by the
Function:
View a measured value. The value is filtered with an 30 ms time constant.
Function:
View the brake power transmitted to an external brake resistor, stated as
an instantaneous value.
Function:
View the brake power transmitted to an external brake resistor. The mean
power is calculated on an average basis for the most recent 120 seconds.
Function:
View the frequency converter heatsink temperature. The cut-out limit is
90 ± 5 °C, and the motor cuts back in at 60 ± 5 °C.
Function:
View the percentage load on the inverter.
Function:
View the inverter nominal current, which should match the nameplate
data on the connected motor. The data are used for calculation of torque,
motor protection, etc.
Function:
View the inverter maximum current, which should match the nameplate
data on the connected motor. The data are used for calculation of torque,
motor protection, etc.
Motor Power
and par.1-25
Motor Nominal
Broken Belt Function
set in par. 22-6*.
TR200 Programming Guide
Motor
Speed.