4-14 Motor Speed High Limit [Hz]
Range:
50/60.0
[par. 4-12 - par. 4-19 Hz]
Hz*
NOTE: Max. output frequency cannot exceed 10% of the inverter switching frequency (par.14-01
quency).
4-16 Torque Limit Motor Mode
Range:
110.0
[0.0 - 1000.0 %]
%*
4-17 Torque Limit Generator Mode
Range:
100.0
[0.0 - 1000.0 %]
%*
4-18 Current Limit
Range:
110.0
[1.0 - 1000.0 %]
%*
4-19 Max Output Frequency
Range:
100.0
[1.0 - 1000.0 Hz]
Hz*
TR200 Programming Guide
Function:
Enter the maximum limit for motor speed. The Motor Speed High Limit
can be set to correspond to the manufacturer's recommended maximum
of the motor shaft. The Motor Speed High Limit must exceed the in par.
4-12
Motor Speed Low Limit
[RPM]
or par.4-12
Motor Speed Low Limit [Hz]
ing on other parameters in the Main Menu and depending on default
settings dependant on global location.
Function:
Enter the maximum torque limit for motor operation. The torque limit is
active in the speed range up to and including the rated motor speed set
in par.1-25
Motor Nominal
the stalling torque, the default setting is 1.1 x the rated motor torque
(calculated value). See also par.14-25
ther details.
If a setting in par.1-00
Configuration Mode
Check
is changed, par.4-16
reset to the default setting.
Function:
Enter the maximum torque limit for generator mode operation. The tor-
que limit is active in the speed range up to and including the rated motor
speed (par.1-25
Motor Nominal
Torque Limit
for further details.
If a setting in par.1-00
Configuration Mode
Check
is changed, par.4-17
matically reset to the default settings.
Function:
Enter the current limit for motor and generator operation. To protect the
motor from reaching the stalling torque, the default setting is 1.1 x the
rated motor current (set in par.1-24
1-00
Configuration Mode
to par.1-28
par.4-16
Torque Limit Motor Mode
tomatically reset to the default settings.
Function:
Enter the maximum output frequency value. par.4-19
quency
specifies the absolute limit on the frequency converter output
frequency for improved safety in applications where accidental over-
speeding must be avoided. This absolute limit applies to all configura-
tions and is independent of the setting in par.1-00
This parameter cannot be adjusted while the motor is running.
Parameter Description
[Hz]. Only par.4-11
Motor Speed Low Limit
will be displayed depend-
Speed. To protect the motor from reaching
Trip Delay at Torque Limit
to par.1-28
Torque Limit Motor Mode
is not automatically
Speed). Refer to par.14-25
to par.1-28
Torque Limit Generator Mode
Motor
Current). If a setting in par.
Motor Rotation Check
to par.4-18
Current Limit
Configuration
Switching Fre-
for fur-
Motor Rotation
Trip Delay at
Motor Rotation
is not auto-
is changed,
are not au-
Max Output Fre-
Mode.
83