Parameter Description
[193]
Sleep Mode
[194]
Broken Belt
[195]
Bypass Valve Control
5-4* Relays
Parameters for configuring the timing and the output functions for the relays.
5-40 Function Relay
Array [8]
(Relay 1 [0], Relay 2 [1]
Option MCB 105: Relay 7 [6], Relay 8 [7] and Relay 9 [8]).
Select options to define the function of the relays.
The selection of each mechanical relay is realised in an array parameter.
Option:
[0] *
No operation
[1]
Control ready
[2]
Drive ready
[3]
Drive rdy/rem ctrl
[4]
Standby / no warning
[5] *
Running
[6]
Running / no warning
[8]
Run on ref/no warn
[9] *
Alarm
[10]
Alarm or warning
[11]
At torque limit
[12]
Out of current range
[13]
Below current, low
[14]
Above current, high
[15]
Out of speed range
[16]
Below speed, low
[17]
Above speed, high
[18]
Out of feedb. range
[19]
Below feedback, low
[20]
Above feedback, high
[21]
Thermal warning
[25]
Reverse
[26]
Bus OK
[27]
Torque limit & stop
[28]
Brake, no brake war
[29]
Brake ready, no fault
[30]
Brake fault (IGBT)
[35]
External Interlock
[36]
Control word bit 11
[37]
Control word bit 12
[40]
Out of ref range
[41]
Below reference, low
[42]
Above ref, high
106
Function:
Default setting for relay 2.
Default setting for relay 1.