Parameter Description
0-11 Programming Set-up
Option:
[0]
Factory setup
[1]
Set-up 1
[2]
Set-up 2
[3]
Set-up 3
[4]
Set-up 4
[9] *
Active Set-up
0-12 This Set-up Linked to
Option:
42
Function:
Select the set-up to be edited (i.e. programmed) during operation; either
the active set-up or one of the inactive set-ups. The set-up number being
edited is displayed in the keypad in (brackets).
cannot be edited but it is useful as a data source to return the other set-
ups to a known state.
Set-up 1
Set-up 4
[1] to
[4] can be edited freely during operation, inde-
pendently of the active set-up.
(i.e. the set-up in which the frequency converter is operating) can also be
edited during operation. Editing parameters in the chosen setup would
normally be done from the keypad but it is also possible from any of the
serial communication ports.
Function:
This parameter only needs to be programmed if changing set-ups is re-
quired whilst the motor is running. It ensures that parameters which are
"not changeable during operation" have the same setting in all relevant
set-ups.
To enable conflict-free changes from one set-up to another whilst the
frequency converter is running, link set-ups containing parameters
which are not changeable during operation. The link will ensure syn-
chronising of the 'not changeable during operation' parameter values
when moving from one set-up to another during operation. 'Not change-
able during operation' parameters can be identified by the label FALSE
in the parameter lists in the section
The par.0-12
This Set-up Linked to
par.0-10
Active Set-up
is selected. Multi set-up can be used to move from
one set-up to another during operation (i.e. while the motor is running).
Example:
Use Multi set-up to shift from Set-up 1 to Set-up 2 whilst the motor is
running. Program parameters in Set-up 1 first, then ensure that Set-up 1
and Set-up 2 are synchronised (or 'linked'). Synchronisation can be per-
formed in two ways:
1. Change the edit set-up to
up
and set par.0-12
This Set-up Linked to
the linking (synchronising) process.
Parameter Lists
.
feature is used when Multi set-up in
Set-up 2
[2] in par.0-11
Programming Set-
Set-up 1
to
[1]. This will start