Read-out and Programming of Indexed Parameters
Parameters are indexed when placed in a rolling stack.
par.15-30
Alarm Log: Error Code
out. Choose a parameter, press [OK], and use the up/down navigation keys to scroll through the value log.
Use par.3-10
Preset Reference
Choose the parameter, press [OK], and use the up/down navigation keys keys to scroll through the indexed
values. To change the parameter value, select the indexed value and press [OK]. Change the value by using the
up/down keys. Press [OK] to accept the new setting. Press [CANCEL] to abort. Press [Back] to leave the parameter.
Initialization to Default Settings
Initialize the frequency converter to default settings in two ways:
Recommended initialization (via par.14-22
1.
Select par.14-22
Operation Mode
2.
Press [OK]
3.
Select "Initialization"
4.
Press [OK]
5.
Cut off the mains supply and wait until the dis-
play turns off.
Note
Resets parameters selected in Personal Menu with default factory setting.
par.14-22
Operation Mode
initializes all except:
par.14-50
RFI Filter
par.8-30
Protocol
par.8-31
Address
par.8-32
Baud Rate
par.8-35
Minimum Response Delay
par.8-36
Maximum Response Delay
par.8-37
Maximum Inter-Char Delay
par.15-00
Operating Hours
to par.15-05
par.15-20
Historic Log: Event
to par.15-22
par.15-30
Alarm Log: Error Code
Manual initialization
1.
Disconnect from mains and wait until the display turns off.
2a.
Press [Status] - [Main Menu] - [OK] at the same time while power up for LCP 102, Graphical Display
2b.
Press [Menu] while power up for LCP 101, Numerical Display
3.
Release the keys after 5 s.
4.
The frequency converter is now programmed according to default settings.
This procedure initializes all except: par.15-00
Note
When you carry out manual initialisation, you also reset serial communication, par.14-50
settings.
Removes parameters selected in par.PC-00
Note
After initialization and power cycling, the display will not show any information until after a couple of minutes.
TR200 Programming Guide
to par.15-33
Alarm Log: Date and Time
as another example:
Operation
Over Volt's
Historic Log: Time
to par.15-32
Alarm Log: Time
Operating
Hours; par.15-03
Pump
Controller.
contain a fault log which can be read
Mode)
6.
Reconnect the mains supply - the frequency con-
verter is now reset.
7.
Change par.14-22
Operation Mode
mal Operation
.
Power
Up's; par.15-04
Over
Temp's; par.15-05
How to Program
Nor-
back to
Over
Volt's.
RFI Filter
and fault log
37