Options for readout output variables:
[0]
No operation
[45]
Bus ctrl.
[48]
Bus ctrl., timeout
[100]
Output frequency
[101]
Reference
[102]
Feedback
[103]
Motor current
[104]
Torque relative to limit
[105]
Torque relative to rated
[106]
Power
[107]
Speed
[108]
Torque
[109]
Max Out Freq
[113]
Ext. Closed Loop
[114]
Ext. Closed Loop
[115]
Ext. Closed Loop
5-60 Terminal 27 Pulse Output Variable
Option:
[0] *
No operation
[45]
Bus ctrl.
[48]
Bus ctrl., timeout
[100]
Output freq. 0-100
[101]
Reference Min-Max
[102]
Feedback +-200%
[103]
Motor cur. 0-Imax
[104]
Torque 0-Tlim
[105]
Torque 0-Tnom
[106]
Power 0-Pnom
[107]
Speed 0-HighLim
[113]
Ext. Closed Loop 1
[114]
Ext. Closed Loop 2
[115]
Ext. Closed Loop 3
5-62 Pulse Output Max Freq #27
Set the maximum frequency for terminal 27, corresponding to the output variable selected in par.5-60
Variable.
This parameter cannot be adjusted while the motor is running.
Range:
5000
[0 - 32000 Hz]
Hz*
5-63 Terminal 29 Pulse Output Variable