Parameter Description
6-02 Fire Mode Live Zero Timeout Function
Option:
[0] *
Off
[1]
Freeze output
[2]
Stop
[3]
Jogging
[4]
Max. speed
6-1* Analog Input 1
Parameters for configuring the scaling and limits for analog input 1 (terminal 53).
6-10 Terminal 53 Low Voltage
Range:
0.07 V* [0.00 - par. 6-11 V]
6-11 Terminal 53 High Voltage
Range:
10.00 V* [par. 6-10 - 10.00 V]
6-12 Terminal 53 Low Current
Range:
4.00
[0.00 - par. 6-13 mA]
mA*
6-13 Terminal 53 High Current
Range:
20.00
[par. 6-12 - 20.00 mA]
mA*
6-14 Terminal 53 Low Ref./Feedb. Value
Range:
0.000 N/
[-999999.999 - 999999.999
A*
N/A]
6-15 Terminal 53 High Ref./Feedb. Value
Range:
50.000
[-999999.999 - 999999.999
N/A*
N/A]
116
Function:
The function set in par.6-01
if the input signal on analog inputs is below 50% of the value defined in
parameter group 6-1* to 6-6* "Terminal xx Low Current" or "Terminal
xx Low Voltage" for a time period defined in par.6-00
Time.
Function:
Enter the low voltage value. This analog input scaling value should cor-
respond to the low reference/feedback value set in par.6-14
Low Ref./Feedb.
Value.
Function:
Enter the high voltage value. This analog input scaling value should cor-
respond to the high reference/feedback value set in par.6-15
High Ref./Feedb.
Value.
Function:
Enter the low current value. This reference signal should correspond to
the low reference/feedback value, set in par.6-14
Feedb.
Value. The value must be set at >2 mA in order to activate the Live
Zero Time-out Function in par.6-01
Function:
Enter the high current value corresponding to the high reference/feed-
back set in par.6-15
Terminal 53 High Ref./Feedb.
Function:
Enter the analog input scaling value that corresponds to the low voltage/
low current set in par.6-10
nal 53 Low
Current.
Function:
Enter the analog input scaling value that corresponds to the high voltage/
high current value set in par.6-11
6-13
Terminal 53 High
Current.
Live Zero Timeout Function
Terminal 53 Low Ref./
Live Zero Timeout
Value.
Terminal 53 Low Voltage
and par.6-12
Terminal 53 High Voltage
TR200 Programming Guide
will be activated
Live Zero Timeout
Terminal 53
Terminal 53
Function.
Termi-
and par.