Trane TR200 Series Programming Manual page 102

Hide thumbs Also See for TR200 Series:
Table of Contents

Advertisement

[84]
SL Digital Output E
[85]
SL Digital Output F
[160]
No alarm
[161]
Running reverse
[165]
Local reference active
[166]
Remote reference active
[167]
Start command active
[168]
Drive in hand mode
[169]
Drive in auto mode
[180]
Clock Fault
[181]
Preventive Maintenance
[190]
No-Flow
[191]
Dry Pump
[192]
End of Curve
[193]
Sleep Mode
[194]
Broken Belt
[195]
Bypass Valve Control
TR200 Programming Guide
See par.13-52
SL Controller
Set dig. out. E high
Smart Logic Action [42]
low whenever the Smart Logic Action [36]
See par.13-52
SL Controller
Set dig. out. F high
Smart Logic Action [43]
low whenever the Smart Logic Action [37]
The output is high when no alarm is present.
The output is high when the frequency converter is running counter
clockwise (the logical product of the status bits 'running' AND 'reverse').
The output is high when par.3-13
Linked to hand auto
3-13
Reference Site
= [0]
keypad is in [Hand on] mode.
The output is high when par.3-13
auto
[0] while the keypad is in [Auto on] mode.
The output is high when there is an active Start command (i.e. via digital
input bus connection or [Hand on] or [Auto on], and no Stop command
is active.
The output is high when the frequency converter is in Hand on mode (as
indicated by the LED light above [Hand on].
The output is high when the frequency converter is in Hand on mode (as
indicated by the LED light above [Auto on].
The clock function has been reset to default (2000-01-01) because of a
power failure.
One or more of the Preventive Maintenance Events programmed in par.
23-10
Maintenance Item
has passed the time for the specified action in
par.23-11
Maintenance
Action.
A No-Flow situation or Minimum Speed situation has been detected if
enabled in par.22-22
Low Speed
A Dry Pump condition has been detected.
A pump running with max. speed for a period of time without reaching
the set pressure has been detected. To enable this function please see
par.AP-50
End of Curve
Function.
The frequency converter/system has turned into sleep mode. See par.
22-4*.
A Broken Belt condition has been detected. This function must be ena-
bled in par.22-60
Broken Belt
The bypass valve control (Digital / Relay output in the frequency con-
verter) is used for compressor systems to unload the compressor during
start-up by using a bypass valve. After the start command is given the
bypass valve will be open until the frequency converter reaches par.
4-11
Motor Speed Low Limit
bypass valve will be closed, allowing the compressor to operate nor-
mally. This procedure will not be activated again before a new start is
initiated and the frequency converter speed is zero during the receiving
of start signal. par.1-71
Start Delay
motor start. The Bypass valve control principle:
Parameter Description
Action. The input will go high whenever the
is executed. The input will go
Set dig. out. E low
Action. The input will go high whenever the
is executed. The input will go
Set dig. out. F low
Reference Site
= [2] Local or when par.
at the same time as the
Reference Site
[1] or
Detection.
Function.
[RPM]). After the limit has been reached the
can be used in order to delay the
is executed.
is executed.
Linked to hand/
101