Trane TR200 Series Programming Manual page 122

Hide thumbs Also See for TR200 Series:
Table of Contents

Advertisement

[141]
Bus ctrl t.o.
[142]
Bus ctrl t.o. 4-20mA
[143]
Ext. CL 1 4-20mA
[144]
Ext. CL 2 4-20mA
[145]
Ext. CL 3 4-20mA
NOTE: Values for setting the Minimum Reference is found in open loop par.3-02
closed loop par.20-13
Minimum Reference/Feedb.
par.3-03
Maximum Reference
6-51 Terminal 42 Output Min Scale
Range:
0.00 %* [0.00 - 200.00 %]
6-52 Terminal 42 Output Max Scale
Range:
100.00
[0.00 - 200.00 %]
%*
TR200 Programming Guide
: 0 - 100%, (0-20 mA)
: 0 - 100%
: 0 - 100%
: 0 - 100%
: 0 - 100%
- values for maximum reference for open loop is found in
and for closed loop par.20-14
Function:
Scale for the minimum output (0 or 4 mA) of the analog signal at terminal
42.
Set the value to be the percentage of the full range of the variable se-
lected in par.6-50
Terminal 42
Function:
Scale for the maximum output (20 mA) of the analog signal at terminal
42.
Set the value to be the percentage of the full range of the variable selec-
ted in par.6-50
Terminal 42
It is possible to get a value lower than 20 mA at full scale by programming
values >100% by using a formula as follows:
mA
desired maximum current
20
/
mA
20
i
e
mA
.
. 10
:
10
mA
Parameter Description
Minimum Reference
Maximum
Reference/Feedb..
Output.
Output.
× 100 %
× 100 % = 200 %