Parameter Description
[49]
Russian
[50]
Thai
[51]
Bahasa Indonesia
0-02 Motor Speed Unit
Option:
[0]
RPM
[1] *
Hz
0-03 Regional Settings
Option:
[0] *
International
[1] *
North America
The setting not used is made invisible.
0-04 Operating State at Power-up
Option:
[0] *
Resume
[1]
Forced stop, ref=old
40
Part of Language package 1
Part of Language package 2
Part of Language package 2
Function:
This parameter cannot be adjusted while the motor is running.
The display showing depends on settings in par.0-02
and par.0-03
Regional
Settings. The default setting of par.0-02
Speed Unit
and par.0-03
Regional Settings
the world the frequency converter is supplied to, but can be re-program-
med as required.
Note
Motor Speed Unit
Changing the
value. It is recommended to select the motor speed unit first, before
modifying other parameters.
Selects display of motor speed variables and parameters (i.e. references,
feedbacks and limits) in terms of motor speed (RPM).
Selects display of motor speed variables and parameters (i.e. references,
feedbacks and limits) in terms of output frequency to the motor (Hz).
Function:
This parameter cannot be adjusted while the motor is running.
The display showing depends on settings in par.0-02
and par.0-03
Regional
Settings. The default setting of par.0-02
Speed Unit
and par.0-03
Regional Settings
the world the frequency converter is supplied to but can be re-program-
med as required.
Sets par.1-20
Motor Power [kW]
par.1-23
Motor Frequency
Sets par.1-21
Motor Power [HP]
1-23
Motor Frequency
to 60 Hz.
Function:
Select the operating mode upon reconnection of the frequency converter
to mains voltage after power down when operating in Hand (local)mode.
Resumes operation of the frequency converter maintaining the same
local reference and the same start/stop condition (applied by [Hand On]/
[Off] on the keypad or Hand Start via a digital input as before the fre-
quency converter was powered down.
Uses saved reference [1] to stop the frequency converter but at the same
time retain in memory the local speed reference prior to power down.
After mains voltage is reconnected and after receiving a start command
(using the keypad [Hand On] button or Hand Start command via a digital
input) the frequency converter restarts and operates at the retained
speed reference.
depends on which region of
will reset certain parameters to their initial
depends on which region of
units to [kW] and the default value of
[50 Hz].
units to HP and the default value of par.
TR200 Programming Guide
Motor Speed Unit
Motor
Motor Speed Unit
Motor