5-3* Digital Outputs
Parameters for configuring the output functions for the output terminals. The 2 solid-state digital outputs are
common for terminals 27 and 29. Set the I/O function for terminal 27 in par.5-01
I/O function for terminal 29 in par.5-02
is running.
[0]
No operation
[1]
Control ready
[2]
Drive ready
[3]
Drive ready / remote con-
trol
[4]
Stand-by / no warning
[5]
Running
[6]
Running / no warning
[8]
Run on reference / no
warning
[9]
Alarm
[10]
Alarm or warning
[11]
At torque limit
[12]
Out of current range
[13]
Below current, low
[14]
Above current, high
[15]
Out of speed range
[16]
Below speed, low
[17]
Above speed, high
[18]
Out of feedback range
[19]
Below feedback low
[20]
Above feedback high
[21]
Thermal warning
[25]
Reverse
[26]
Bus OK
[27]
Torque limit and stop
[28]
Brake, no warning
[29]
Brake ready, no fault
TR200 Programming Guide
Terminal 29
Mode. These parameters cannot be adjusted while the motor
The digital outputs can be programmed with these functions:
Default for all digital outputs and relay outputs
The control board receives supply voltage.
The frequency converter is ready for operation and applies a supply sig-
nal on the control board.
The frequency converter is ready for operation and is in Auto On mode.
The frequency converter is ready for operation. No start or stop com-
mand is been given (start/disable). There are no warnings.
The motor is running.
The output speed is higher than the speed set in par.1-81
Function at Stop
[RPM]. The motor is running and there are no warnings.
The motor runs at reference speed.
An alarm activates the output. There are no warnings.
An alarm or a warning activates the output.
The torque limit set in par.4-16
been exceeded.
The motor current is outside the range set in par.4-18
The motor current is lower than set in par.4-50
The motor current is higher than set in par.4-51
The output speed is outside the range set in par.4-52
Low
and par.4-53
Warning Speed
The output speed is lower than the setting in par.4-52
Low.
The output speed is higher than the setting in par.4-53
High.
The feedback is outside the range set in par.4-56
Low
and par.4-57
Warning Feedback
The feedback is below the limit set in par.4-56
The feedback is above the limit set in par.4-57
The thermal warning turns on when the temperature exceeds the limit
in the motor, the frequency converter, the brake resistor, or the thermis-
tor.
Reversing. Logic '1' =
relay activated, 24 V DC when CW rotation of the
motor. Logic '0' = relay not activated, no signal, when CCW rotation of
the motor.
Active communication (no time-out) via the serial communication port.
Use in performing a coasting stop and in torque limit condition. If the
frequency converter has received a stop signal and is at the torque limit,
the signal is Logic '0'.
The brake is active and there are no warnings.
The brake is ready for operation and there are no faults.
Parameter Description
Terminal 27 Mode
Torque Limit Motor Mode
or par. 1-17 has
Current
Warning Current
Warning Current
Warning Speed
High.
Warning Speed
Warning Speed
Warning Feedback
High.
Warning Feedback
Warning Feedback
and set the
Min Speed for
Limit.
Low.
High.
Low.
High.
99