Parameter Description
4-5* Adj. Warnings
Define adjustable warning limits for current, speed, reference and feedback.
Note
Not visible in display, only in Trane Drive Utility.
Warnings are shown on display, programmed output or serial bus.
4-50 Warning Current Low
Range:
0.00 A* [0.00 - par. 4-51 A]
4-51 Warning Current High
Range:
par.
[par. 4-50 - par. 16-37 A]
16-37 A*
4-53 Warning Speed High
Range:
par. 4-13
[par. 4-52 - par. 4-13 RPM] Enter the n HIGH value. When the motor speed exceeds this limit
RPM*
NOTE: Any changes in par.4-13
High
to the same value as set in par.4-13
If a different value is needed in par.4-53
4-13
Motor Speed High Limit
84
Function:
Enter the I LOW value. When the motor current falls below this limit
(I LOW ), the display reads CURRENT LOW. The signal outputs can be
programmed to produce a status signal on terminal 27 or 29 and on relay
output 01 or 02. Refer to the drawing in this section.
Function:
Enter the I HIGH value. When the motor current exceeds this limit
(I HIGH ), the display reads CURRENT HIGH. The signal outputs can be
programmed to produce a status signal on terminal 27 or 29 and on relay
output 01 or 02. Refer to the drawing in this section.
Function:
(n HIGH ), the display reads SPEED HIGH. The signal outputs can be pro-
grammed to produce a status signal on terminal 27 or 29 and on relay
output 01 or 02. Programme the upper signal limit of the motor speed,
n HIGH , within the normal working range of the frequency converter. Re-
fer to the drawing in this section.
Motor Speed High Limit [RPM]
Motor Speed High Limit
Warning Speed
[RPM]!
will reset the value in par.4-53
[RPM].
High, it must be set after programming of par.
Warning Speed
TR200 Programming Guide