Trane TR200 Series Programming Manual page 133

Hide thumbs Also See for TR200 Series:
Table of Contents

Advertisement

Parameter Description
[1]
Bus
[2]
Logic AND
[3] *
Logic OR
NOTE: This parameter is active only when par.8-01
8-7* BACnet
BACnet configuration
8-70 BACnet Device Instance
Range:
1 N/A*
[0 - 4194304 N/A]
NOTE: This parameter is active only when par.8-30
8-72 MS/TP Max Masters
Range:
127 N/
[0 - 127 N/A]
A*
NOTE: This parameter is active only when par.8-30
8-73 MS/TP Max Info Frames
Range:
1 N/A*
[1 - 65534 N/A]
NOTE: This parameter is active only when par.8-30
8-74 "I-Am" Service
Option:
[0] *
Send at power-up
[1]
Continuously
NOTE: This parameter is active only when par.8-30
8-75 Initialisation Password
Range:
0 N/A*
[0 - 0 N/A]
NOTE: This parameter is active only when par.8-30
8-8* FC Port Diagnostics
These parameters are used for monitoring the Bus communication via the FC Port.
8-80 Bus Message Count
Range:
0 N/A*
[0 - 0 N/A]
132
Activates Preset Reference selection via the serial communication port
or fieldbus option.
Activates Preset Reference selection via the fieldbus/serial communica-
tion port, AND additionally via one of the digital inputs.
Activates the Preset Reference selection via the fieldbus/serial commu-
nication port OR via one of the digital inputs.
Control Site
is set to [0]
Function:
Enter a unique ID number for the BACnet device.
Protocol
is set to [9]
Function:
Define the address of the master which holds the highest address in this
network. Decreasing this value optimizes polling for the token.
Protocol
is set to [9]
Function:
Define how many info/data frames the device is allowed to send while
holding the token.
Protocol
is set to [9]
Function:
Choose whether the device should send the "I-Am" service message only
at power-up or continuously with an interval of approx. 1 min.
Protocol
is set to [9]
Function:
Enter the password needed for execution of Drive Re-initialization from
BACnet.
Protocol
is set to [9]
Function:
This parameter shows the number of valid telegrams detected on the
bus.
Digital and control word
.
Drive Option
.
Option
.
Option
.
Option
.
Drive Option
.
TR200 Programming Guide

Hide quick links:

Advertisement

Table of Contents
loading