Trane TR200 Series Programming Manual page 121

Hide thumbs Also See for TR200 Series:
Table of Contents

Advertisement

Parameter Description
6-47 Term. X30/12 Live Zero
Option:
[0] *
Disabled
[1] *
Enabled
6-5* Analog Output 1
Parameters for configuring the scaling and limits for analog output 1, i.e. Terminal 42. Analog outputs are current
outputs: 0/4 – 20 mA. Common terminal (terminal 39) is the same terminal and has the same electrical potential
for analog common and digital common connection. Resolution on analog output is 12 bit.
6-50 Terminal 42 Output
Option:
[0] *
No operation
[100]
Output freq. 0-100
[101]
Reference Min-Max
[102]
Feedback +-200%
[103]
Motor cur. 0-Imax
[104]
Torque 0-Tlim
[105]
Torque 0-Tnom
[106]
Power 0-Pnom
[107] *
Speed 0-HighLim
[113]
Ext. Closed Loop 1
[114]
Ext. Closed Loop 2
[115]
Ext. Closed Loop 3
[130]
Out frq 0-100 4-20mA
[131]
Reference 4-20mA
[132]
Feedback 4-20mA
[133]
Motor cur. 4-20mA
[134]
Torq.0-lim 4-20 mA
[135]
Torq.0-nom 4-20mA
[136]
Power 4-20mA
[137]
Speed 4-20mA
[139]
Bus ctrl.
[140]
Bus ctrl. 4-20 mA
120
Function:
This parameter makes it possible to disable the Live Zero monitoring.
E.g. to be used if the analog outputs are used as part of a decentral I/O
system (e.g. when not part of any frequency converter related control
functions, but feeding a Building Management System with data)
Function:
Select the function of Terminal 42 as an analog current output. A motor
current of 20 mA corresponds to I max .
: 0 - 100 Hz, (0-20 mA)
: Minimum reference - Maximum reference, (0-20 mA)
: -200% to +200% of par.20-14
: 0 - Inverter Max. Current (par.16-37
: 0 - Torque limit (par.4-16
: 0 - Motor rated torque, (0-20 mA)
: 0 - Motor rated power, (0-20 mA)
: 0 - Speed High Limit (par.4-13
4-14
Motor Speed High Limit
: 0 - 100%, (0-20 mA)
: 0 - 100%, (0-20 mA)
: 0 - 100%, (0-20 mA)
: 0 - 100 Hz
: Minimum Reference - Maximum Reference
: -200% to +200% of par.20-14
: 0 - Inverter Max. Current (par.16-37
: 0 - Torque limit (par.4-16
: 0 - Motor rated torque
: 0 - Motor rated power
: 0 - Speed High Limit (4-13 and 4-14)
: 0 - 100%, (0-20 mA)
: 0 - 100%
Maximum
Reference/Feedb., (0-20 mA)
Inv. Max.
Current), (0-20 mA)
Torque Limit Motor
Mode), (0-20 mA)
Motor Speed High Limit [RPM]
[Hz]), (0-20 mA)
Maximum Reference/Feedb.
Inv. Max.
Current)
Torque Limit Motor
Mode)
TR200 Programming Guide