6-53 Terminal 42 Output Bus Control
Range:
0.00 %* [0.00 - 100.00 %]
6-54 Terminal 42 Output Timeout Preset
Range:
0.00 %* [0.00 - 100.00 %]
6-6* Analog Output 2 MCB 101
Analog outputs are current outputs: 0/4 - 20 mA. Common terminal (terminal X30/8) is the same terminal and
electrical potential for analog common connection. Resolution on analog output is 12 bit.
6-60 Terminal X30/8 Output
6-60 Terminal X30/8 Output
Option:
[0] *
No operation
[100]
Output freq. 0-100
[101]
Reference Min-Max
[102]
Feedback +-200%
[103]
Motor cur. 0-Imax
[104]
Torque 0-Tlim
[105]
Torque 0-Tnom
[106]
Power 0-Pnom
[107]
Speed 0-HighLim
[113]
Ext. Closed Loop 1
[114]
Ext. Closed Loop 2
[115]
Ext. Closed Loop 3
[130]
Out frq 0-100 4-20mA
[131]
Reference 4-20mA
[132]
Feedback 4-20mA
[133]
Motor cur. 4-20mA
[134]
Torq.0-lim 4-20 mA
[135]
Torq.0-nom 4-20mA
[136]
Power 4-20mA
[137]
Speed 4-20mA
[139]
Bus ctrl.
[140]
Bus ctrl. 4-20 mA
[141]
Bus ctrl t.o.
[142]
Bus ctrl t.o. 4-20mA
[143]
Ext. CL 1 4-20mA
[144]
Ext. CL 2 4-20mA
[145]
Ext. CL 3 4-20mA
TR200 Programming Guide
Function:
Holds the level of Output 42 if controlled by bus.
Function:
Holds the preset level of Output 42.
In case of a bus timeout and a timeout function is selected in par.
6-50
Terminal 42 Output
the output will preset to this level.
Function:
Parameter Description
123