Trane TR200 Series Programming Manual page 227

Hide thumbs Also See for TR200 Series:
Table of Contents

Advertisement

Parameter Description
[11]
Drive cooling fan
[12]
System health check
[13]
Warranty
[20]
Maintenance Text 0
[21]
Maintenance Text 1
[22]
Maintenance Text 2
[23]
Maintenance Text 3
[24]
Maintenance Text 4
[25]
Maintenance Text 5
23-11 Maintenance Action
Option:
[1] *
Lubricate
[2]
Clean
[3]
Replace
[4]
Inspect/Check
[5]
Overhaul
[6]
Renew
[7]
Check
[20]
Maintenance Text 0
[21]
Maintenance Text 1
[22]
Maintenance Text 2
[23]
Maintenance Text 3
[24]
Maintenance Text 4
[25]
Maintenance Text 5
23-12 Maintenance Time Base
Option:
[0] *
Disabled
[1]
Running Hours
[2]
Operating Hours
[3]
Date & Time
226
Function:
Select the action to be associated with the Preventive Maintenance
Event.
Function:
Select the time base to be associated with the Preventive Maintenance
Event.
Disabled
[0] must be used when disabling the Preventive Maintenance
Event.
Running Hours
[1] is the number of hours the motor has been running.
Running hours are not reset at power-on. The
must be specified in par.23-13
Operating Hours
[2] is the number of hours the frequency converter has
been running. Operating hours are not reset at power-on. The
nance Time Interval
must be specified in par.23-13
Interval.
Date & Time
[3] uses the internal clock. The date and time of the next
maintenance occurrence must be specified in par.23-14
Date and
Time.
Maintenance Time Interval
Maintenance Time
Interval.
Maintenance Time
Maintenance
TR200 Programming Guide
Mainte-

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents