Appendix 3.2 Link special registers (SW)

Number
Name
Multiple temporary
SW0003
error invalid station
(603
)
H
specification
SW0004
(604
)
H
SW0005
Temporary error
(605
)
H
invalid station
SW0006
specification
2
(606
)
H
SW0007
(607
)
H
SW0008
Loop test station
(608
)
setting
H
SW0009
Monitoring time
(609
)
setting
H
2: Only the bit for the first station number is turned on.
App - 28
Data is stored in the link special registers SW000 to SW001F by the program, and data
is automatically stored in SW0020 to SW01FF. The values in parentheses in the
number column indicate the buffer memory addresses.
When the standby master station is controlling the data link, availability is basically
identical to that of the master station.
When the standby master station is operating as a local station, availability is identical
to that of a local station.
POINT
Do not write data to the area of the No. which does not exist in the link special
register (SW) list.
Writing data to the area of the No. which does not exist in the list may cause
malfunction of the programmable controller system.
The following table lists the link special registers.
Description
Select whether multiple temporary error invalid stations are
specified.
00
: Specifies multiple stations indicated by SW0004 to
SW0007.
01 to 64: Specifies a single station from 1 to 64.
(The specified number indicates the station number of a
temporary error invalid station.)
Specifies a temporary error invalid station.
0: Not specified as a temporary error invalid station
1: Specified as a temporary error invalid station
b15
b14
b13
SW0004
16
15
14
SW0005
32
31
30
SW0006
48
47
46
SW0007
64
63
62
Numbers 1 to 64 in the above table indicate the station numbers.
Error invalid stations, reserved stations and any station of the
number higher than the max. are not specified
0
: Entire system (executed for all stations)
01 to 64
: Specified station only
Default value: 0
Sets the monitoring time when a dedicated instruction is used.
Default value: 10 (seconds)
Setting range: 0 to 360 (seconds)
The monitoring time of 360 seconds will be used if a value
outside of the above setting range is specified.
If a value is set in SW000B, time elapsed until error completion of a
dedicated instruction is as follows:
(Number of retries + 1) x Monitoring time
b12
to
b3
b2
b1
to
13
4
3
2
to
29
20
19
18
45
to
36
35
34
61
to
52
51
50
.
Availability
(
: Available,
Online
Master station
Local station
b0
1
17
33
49
APPENDIXES
: Not available)
Offline
(To the next page)
App - 28