Item
Set the total number of connected stations in the CC-Link system including
reserved stations for "Total Module Connected".
Total Module Connected
Default value: 64 (modules)
Setting range: 1 to 64 (modules)
Set the remote input (RX) refresh device.
Default value: Blank
Remote Input (RX)
Setting range: Device name - Select from X, M, L, B, D, W, R or ZR.
Set the remote output (RY) refresh device.
Default value: Blank
Setting range: Device name - Select from
Remote Output (RY)
Set the remote register (RWr) refresh device.
Default value: Blank
Remote Register (RWr)
Setting range: Device name - Select from M, L, B, D, W, R or ZR.
Set the remote register (RWw) refresh device.
Default value: Blank
Setting range: Device name - Select from
Remote Register (RWw)
Set the link special relay (SB) refresh device.
Default value: Blank
Special Relay (SB)
Setting range: Device name - Select from M, L, B, D, W, R, SB or ZR.
Set the link special register (SW) refresh device.
Default value: Blank
Special Register (SW)
Setting range: Device name - Select from M, L, B, D, W, R, SW or ZR.
Set the data link status when a master station programmable controller
CPU error occurs.
PLC Down Select
Default value: Stop
Setting range: Stop
Set whether the link scan for the sequence scan is synchronous or
asynchronous.
Scan Mode Setting
Default value: Asynchronous
Setting range: Asynchronous
7 - 31
Description
Device number - Within the range of the device points that
the CPU has.
Y, M, L, B, T, C, ST, D, W, R or ZR.
Device number - Within the range of the device points that
the CPU has.
Device number - Within the range of the device points that
the CPU has.
M, L, B, T, C, ST, D, W, R or ZR.
Device number - Within the range of the device points that
the CPU has.
Device number - Within the range of the device points that
the CPU has.
Device number - Within the range of the device points that
the CPU has.
Continue
Synchronous
7 PARAMETER SETTINGS
Standby
Master
Local
Master
Reference
station
station
station
Section
Section
Section
: Available,
: Not available
7 - 31
――
――
――
――
――
――
――
8.2.3,
8.2.6
8.3.7