Mitsubishi LJ61BT11 User Manual page 410

Melsec l series cc-link system master/local module
Table of Contents

Advertisement

Appendix 4.3 Transmission delay time of master station
compatible slave station)
Calculation
With block guarantee of cyclic data per station
value
Asynchronous mode
Normal
(SM×n)+(LS×1)+Rd
value
Max. value
(SM×n)+(LS×2)+Rd
Calculation
With block guarantee of cyclic data per station
value
Asynchronous mode
Normal
(20×1)+(3×1)+1.5
value
= 24.5ms
(20×1)+(3×2)+1.5
Max. value
= 27.5ms
App - 46
(1) Master station (RX)
This indicates the time from when a signal is input to a remote device station until
the corresponding CPU device turns ON (OFF) or CPU device data is changed.
[Expression]
The meanings of symbols in the table are as follows:
SM :
LS :
n
:
Rd :
Synchronous mode
{(SM×n)×1}+Rd
{(SM×n)×2}+Rd
Calculation example:
Master station sequence scan time of 20ms, link scan time of 3ms, and
remote device station processing time of 1.5ms
Synchronous mode
{(20×1)×1}+1.5
= 21.5ms
{(20×1)×2}+1.5
= 41.5ms
Remote device station (RX), (RWr)
Master station sequence scan time
Link scan time
LS÷SM (Digits past the decimal point are rounded up to the
nearest integer.)
Remote device station processing time
Without block guarantee of cyclic data per station
Asynchronous mode
SM+(LS×1)+Rd
SM+(LS×2)+Rd
Without block guarantee of cyclic data per station
Asynchronous mode
20+(3×1)+1.5
= 24.5ms
20+(3×2)+1.5
= 27.5ms
remote device station (Ver.1
Synchronous mode
{(SM×n)×1}+Rd
{(SM×n)×2}+Rd
Synchronous mode
{(20×1)×1}+1.5
= 21.5ms
{(20×1)×2}+1.5
= 41.5ms
APPENDIXES
App - 46

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

L26cpu-bt

Table of Contents