Program
Data link stop
Host data link status
(X01)
Refresh instruction
(SB0003)
Data link stop
(SB0002)
Data link stop complete
(SB0045)
G(P).RLPASET instruction
Direction device
Complete device
Status display device
at completion
9 - 37
(C) There are two types or interlock signals for the G(P).RLPASET instruction:
the completion device (D) and status display device at completion (D) + 1.
1)
Completion device
Turns ON in the END Processing of the scan where the
G(P).RLPASET instruction is completed, and turns OFF in the next
END processing.
2)
Status display device at completion
Turns On and OFF depending on the completion status of the
G(P).RLPASET instruction.
Normal completion
Abnormal completion : Turns ON in the END processing of the scan
(D) After executing the G(P).RLPASET instruction, turn on SB0003
(refresh instruction) to refresh cyclic data.
[When all the stations are normal]
END
END
processing
processing
processing
Refresh stop
9. DEDICATED INSTRUCTIONS AND PROGRAMMING
: Stays OFF and does not change.
where the G(P).RLPASET instruction is
completed, and turns OFF in the next END
processing.
END
END
processing
END
END
processing
processing
Refresh start
Data link start
G(P).RLPASET
instruction
completion
ON
ON
Abnormal completion
1 scan
END
processing
9 - 37