(2) Remote net additional mode
[Expression]
KM1+(KM2+KM3)
E= RX+RX2+RY+RY2+SB
16
RX
: Points of the remote input (RX) refreshed by the master/local station
RX2
: Points of the ver.2 remote input (RX) refreshed by the master/local
station
RY
: Points of the remote output (RY) refreshed by the master/local station
RY2
: Points of the ver.2 remote output (RY) refreshed by the master/local
station
RWw : Points of the remote register (RWw) refreshed by the master/local
station
RWw2 : Points of the ver.2 remote register (RWw) refreshed by the master/local
station
RWr
: Points of the remote register (RWr) refreshed by the master/local station
RWr2 : Points of the ver.2 remote register (RWr) refreshed by the master/local
station
SB
: Points of the link special relay (SB) refreshed by the master/local station
SW
: Points of the link special register (SW) refreshed by the master/local
station
KM1, KM2, KM3, KM4
With block
guarantee of cyclic
data per station
function set
0.55
0.73
0.29
0.47
0.45
0.71
POINT
The number of CC-Link modules in the expression includes the built-in CC-Link
function.
(Example) When using the L26CPU-BT and the LJ61BT11 is mounted, the number
of CC-Link modules counted is two.
E+(No. of CC-Link modules-1) KM4 [ms]
+RWw+RWw2+RWr+Rwr2+SW
: Constant
KM1
Without block
guarantee of cyclic
data per station
function set
0.43
0.60
0.17
0.35
0.26
0.53
-3
KM2 ( 10
)
KM3 ( 10
0.38
0.05
0.23
0.03
0.35
0.05
APPENDIXES
-3
)
KM4
0.2
0.2
0.2
App - 64