8.2.3 Data link status setting in case of master station programmable controller CPU failure

8 - 24
This function sets the data link status (stop/continue) in case that an "error that stops
the operation" occurs in the master station programmable controller CPU when the
system does not have a standby master station.
When it is set to "continue", the data link among local stations can be continued.
For the status of each station at error occurrence, refer to Section 8.2.6.
POINT
(1) The data link continues when the master station programmable controller CPU
falls into an "error that stops the operation".
(2) With a standby master station setting, the data link will not continue when the
master station programmable controller CPU is down even if the data link
status at CPU down is set to "Continue". The standby master function
overrides the setting and the data link control is switched to the standby
master station.
[Setting method]
Specify "PLC Down Select" in the Network Parameter setting of GX
Works2. (Refer to Sections 7.2 to 7.5.)
8 FUNCTIONS
8 - 24