Mitsubishi LJ61BT11 User Manual page 429

Melsec l series cc-link system master/local module
Table of Contents

Advertisement

App - 65
(Example)
When the L26CPU-BT is used as the master station, and 1024 points of
RX, 896 points of RX2, 1024 points of RY, 896 points of RY2, 128
points of RWw, 128 points of RWw2, 128 points of RWr, 128 points of
RWr2, 512 points of SB and 512 points of SW are refreshed.
(a) When the block guarantee of cyclic data per station is enabled
RX+RX2+RY+RY2+SB
E=
1024+896+1024+896+512
=
=1296
KM1+(KM2+KM3)
=0.29+(0.00023+0.00003) 1296+(1-1) 0.2
=0.62696
=0.63 [ms]
(b) When the block guarantee of cyclic data per station is not
enabled
KM1+(KM2+KM3)
=0.17+(0.00023+0.00003) 1296+(1-1) 0.2
=0.50696
=0.51 [ms]
+RWw+RWw2+RWr+RWr2+SW
16
+128+128+128+128+512
16
E+(Number of CC-Link modules-1) KM4
E+(Number of CC-Link modules-1) KM4