Expanded Cyclic Setting - Mitsubishi LJ61BT11 User Manual

Melsec l series cc-link system master/local module
Table of Contents

Advertisement

3.4.1 Expanded cyclic setting

Master station
Ver.2 mode
Ver. 2
Station number 1
compatible
Station number 2
remote
output RY
Station number 3
Station number 4
Station number 5
Station number 6
Station number 7
to
3 - 13
When increasing the number of link points, select the remote net ver.2 mode or the
remote net additional mode.
(1) Remote net ver.2 mode
This mode is designed to configure a new system.
The number of link points can be increased as indicated below.
Per station, RX/RY can be increased to up to 128 points and RWw/RWr to up to
32 points.
Per CC-Link network, RX/RY can be increased to up to 8192 points and
RWw/RWr to up to 2048 points.
Remote I/O station
(Station number 1:
Occupies 1 station)
Output
POINT
(1) In the remote net ver.2 mode, the remote registers of the remote I/O station are
set to 0 points.
(2) When the ver.2 compatible slave station is added or deleted, the refresh devices
of the programmable controller CPU will vary by the number of points set to the
added or deleted slave station in the slave stations of the station numbers after
the added or deleted slave station. Confirm the varying number of points in
Section 3.2 (1).
Remote device station
Ver. 2 compatible
(Station number 2:
Occupies 4 stations)
Occupies 1 station)
Remote output RY
quadruple
3 SPECIFICATIONS
Local station
Remote device station
Ver.2 mode
(Station number 3:
(Station number 7:
Occupies 1 station)
Remote input RX
Station number 1
Station number 2
Station number 3
Station number 4
Station number 5
Station number 6
Remote output RY
Station number 7
to
double
Ver. 2 compatible
octuple
3 - 13

Hide quick links:

Advertisement

Table of Contents
loading