11 EXAMPLE OF COMMUNICATION BETWEEN THE MASTER STATION AND REMOTE DEVICE STATIONS
11 - 18
Set parameters as follows.
2) Procedure registration of AJ65VBTCU-68DAVN
Click the "Regist Procedure" of the target station number "4".
The details to be set are as follows:
Set channels 1 and 2 to Analog output enable. (the first condition)
Set the output range of channel 1 to 0 - 5V, and channel 2 to User
range setting 1. (the second condition)
Set the HOLD/CLEAR setting of channels 1, 2 to CLEAR. (the third
condition)
Turn the Initial data processing completed flag to ON (the forth
condition).
Turn the Initial data setting request flag to ON (the fifth condition).
Turn the Initial data processing completed flag to OFF (the sixth
condition).
Turn the Initial data setting request flag to OFF (the seventh
condition).
Set parameters as follows.
11 - 18