8.3.9 Remote I/O station points setting

Programmable
controller CPU
Master station
Remote output RY
number 2
Station number 3
Y
8 - 75
The points of each remote I/O station can be set to 8, 16 or 32 points.
This saves the refresh device points of the programmable controller CPU and link
refresh time.
The remote I/O station points setting can be used in the remote net ver. 2 mode only.
For parameter setting, use GX Works2.
This function cannot be executed if the dedicated instruction is used for parameter
setting. This function can be executed when read/write from/to the CPU devices is
performed according to the I/O points of each station at cyclic data refresh using the
FROM/TO instruction.
Remote I/O station
(Station number 1:
Occupies 1 station)
Station
Station
number 1
Station
number 4
to
8-point output module
Device area when remote I/O points setting is made
Device area when remote I/O points setting is not made
POINT
Set points to even-numbered 8-point setting remote I/O stations consecutively. If
points are set to odd-numbered 8-point setting remote stations, select 8 points + 8
points reserved in the "Remote Station Points" setting of the last of the consecutive
remote I/O stations.
Remote I/O station
(Station number 1:
Master station
Occupies 1 station)
Remote output RY
Station
Station
number 2
number 1
Station
reserved
number 3
Station
number 4
8points+8points
(reserved)
to
8-point output module
Odd-numbered 8-point setting remote stations cannot be set for 8 remote station
points.
Remote I/O station
(Station number 1:
Master station
Occupies 1 station)
Remote output RY
Station
Station
number 2
number 1
Station
number 3
Station number 4
Cannot be set.
to
8-point output module
Refer to Section 7.3 for parameter setting.
Remote I/O station
(Station number 2:
Occupies 1 station)
Y07 to Y00
Y07 to Y00
8-point output module
Remote I/O station
(Station number 2:
Occupies 1 station)
Y07 to Y00
Y07 to Y00
8-point output module
Remote I/O station
(Station number 2:
Occupies 1 station)
Y07 to Y00
Y07 to Y00
8-point output module
Remote I/O station
Remote I/O station
(Station number 3:
(Station number 4:
Occupies 1 station)
Occupies 1 station)
Y0F to Y00
16-point output module
32-point output module
Remote I/O station
Remote I/O station
(Station number 3:
(Station number 4:
Occupies 1 station)
Occupies 1 station)
Y07 to Y00
Y0F to Y00
Y1F to Y10
8-point output module
32-point output module
Remote I/O station
Remote I/O station
(Station number 3:
(Station number 4:
Occupies 1 station)
Occupies 1 station)
Y07 to Y00
Y0F to Y00
Y1F to Y10
8-point output module
32-point output module
8 FUNCTIONS
Y0F to Y00
Y1F to Y10
8 - 75