(2) Setting method
8 - 38
Perform the setting using GX Works2.
(a) Setting the master station
First, set "Type" in the Network Parameter setting.
Master station that was down returns to system operation: Master Station
(Duplex Function)
Master station that was down does not return to system operation: Master
Station
Next, set the "Standby Master Station No." of the network parameter.
Setting range: 1 to 64 (blank means no specification for standby master
station)
Default
: blank (no specification for standby master station)
(b) Setting the standby master station
Set "Type" in the Network Parameter setting to "Standby Master Station".
Set the mode according to the mode setting of the master station.
8 FUNCTIONS
8 - 38