Appendix 7 When Using the GX Developer

Appendix 7.1 Compatible software package

Appendix 7.2 Operation comparison

App - 68
Refer to the following manual.
MELSEC-L CPU Module User's Manual (Hardware Design, Maintenance and
Inspection)
The following shows the operating method to use the GX Developer.
For details on the operation of GX Developer, refer to the Operating Manual of GX
Developer.
(1) How to operate the wiring check
[Example of wiring check]
Specify the "Remote input (RX)" for the master station to "X1000" and the "Remote
output (RY)" to "Y1000" with the GX Developer.
Master station
(a) Checking the wiring between the input module and an external device
1) Turn ON the switch corresponding to the external device "X0," which is
connected to the input module of station number 1.
2) Using the GX Developer, set "X1000" in the "Device:" field by choosing
[Online]
3) If X1000 is ON, the connection between the input module and external
device has been properly performed.
(b) Checking the wiring between the output module and an external device
1) Using the GX Developer, set "Y1020" in the "Device:" field for the "Bit
device" by choosing [Online]
on "FORCE ON".
2) If the connection between the output module and external device is
properly performed, the indicator lamp corresponding to the external
device "Y00" is lit.
Input module
Remote I/O station
(Station number 1, number
of occupied stations 1)
X00
[Monitor]
[Device batch] and then click on "Start monitor".
[Debug]
Output module
Remote I/O station
(Station number 2, number
of occupied stations 1)
ON
[Device test] and then click
APPENDIXES
ON
Y00