Item
Set the refresh device of the Ver.2 compatible remote input (RX).
Default value: Blank
Ver.2 Remote Input (RX)
Setting range: Device name - Select from X, M, L, B, D, W, R or ZR.
Set the refresh device of the Ver.2 compatible remote output (RY).
Default value: Blank
Ver.2 Remote Output
Setting range: Device name - Select from
(RY)
Set the refresh device of the Ver.2 compatible remote register (RWr).
Default value: Blank
Ver.2 Remote Register
Setting range: Device name - Select from M, L, B, D, W, R or ZR.
(RWr)
Set the refresh device of the Ver.2 compatible remote register (RWw).
Default value: Blank
Ver.2 Remote Register
Setting range: Device name - Select from
(RWw)
Set the link special relay (SB) refresh device.
Default value: Blank
Special Relay (SB)
Setting range: Device name - Select from M, L, B, D, W, R, SB or ZR.
Set the link special register (SW) refresh device.
Default value: Blank
Special Register (SW)
Setting range: Device name - Select from M, L, B, D, W, R, SW or ZR.
Sets the number of retries when a communication error occurs.
Retry Count
Default value: 3 (times)
Setting range: 1 to 7 (times)
Set the number of modules that can return to system operation by a single
Automatic Reconnection
link scan.
Station Count
Default value: 1 (module)
Setting range: 1 to 10 (modules)
Set the station number for the standby master station.
Standby Master Station
Default value: Blank (No standby master station specified)
No.
Setting range: Blank, 1 to 64 (Blank: No standby master station specified)
Set the data link status when a master station programmable controller
CPU error occurs.
PLC Down Select
Default value: Stop
Setting range: Stop
7 - 23
Description
Device number - Within the range of the device points that
the CPU has.
Y, M, L, B, T, C, ST, D, W, R or ZR.
Device number - Within the range of the device points that
the CPU has.
Device number - Within the range of the device points that
the CPU has.
M, L, B, T, C, ST, D, W, R or ZR.
Device number - Within the range of the device points that
the CPU has.
Device number - Within the range of the device points that
the CPU has.
Device number - Within the range of the device points that
the CPU has.
Continue
7 PARAMETER SETTINGS
Standby
Master
Local
Master
Reference
station
station
station
Section
Section
Section
Section
: Available,
: Not available
(To the next page)
7 - 23
――
――
――
――
――
――
――
8.2.2
8.2.7
8.2.3,
8.2.6