14.2 Image of Link Scan and Link Refresh by Cyclic Transmission

The following shows a transmission image of link device remote input RX, remote
output RY, and the remote registers RWr and RWw.
1) Configure the link refresh of CC-Link IE field network in "Refresh Parameters" in Network Parameter of the CC-Link IE
field network master station.
2) Configure the inter-device transfer settings of the head module by selecting "PLC Parameter" - "Operation Setting" in
the head module. (Refer to 14.3.2 (2).)
3) Configure the CC-Link automatic refresh in Network Parameter of LJ61BT11, which is connected on the head module.
(Refer to 14.3.2 (3).)
The head module link devices (RX/RY/RWr/RWw) are assigned as follows.
• Remote input (RX): Assigned from input (X0).
• Remote output (RY): Assigned from output (Y0).
• Remote register (RWr): Assigned from link register (W1000).
• Remote register (RWw): Assigned from link register (W0).
14 - 2
14 EXAMPLE OF COMMUNICATION WHEN MOUNTING MODULES ON THE HEAD MODULE