Mitsubishi LJ61BT11 User Manual page 213

Melsec l series cc-link system master/local module
Table of Contents

Advertisement

(2) Operation error
(3) Program example
Programmable controller CPU
9 - 30
In the following cases, operation error occurs; the error flag (SM0) turns ON and
the error code is stored in SD0.
Error code
When the module specified by Un is not an intelligent function module.
2112
When the module specified by Un is not a special function module.
4002
When an attempt was made to execute an unsupported instruction.
4003
When the number of devices in the instruction is incorrect.
4004
When the instruction specifies a device that cannot be used.
When the setting for number of points to write (n3) is outside of the setting range.
4100
When the station number specified with n1 does not exist.
Device memory
When X0 is turned ON, the following example program writes 10-word data from
D0 to the automatic update buffer offset value starting from 100 (400
intelligent device station) in the master module.
(When the link special register (SW) refresh device is set to SW0000)
9. DEDICATED INSTRUCTIONS AND PROGRAMMING
Description of operation error
Master module
(Start I/O number 40
)
H
Automatic update buffer
Intelligent device station
(Station number 1)
Buffer memory
300
H
Automatic update
buffer memory
5FF
H
of the
H
Dedicated instruction
execution
9 - 30